More Info

ASF Leak Detector Type “VAKUMATIK IV F R34” - VACUUM PRINCIPLE

Article No.: 4121 0040 (Basic Unit)

Applications

  • The leak detector can be used on single-walled tanks with leak protection lining and a suction line to the vessel bottom out.
  • The leak detector can also be used on double-walled tanks with a general building approval (certificate sooner), provided a suction line to the vessel bottom is present. The conditions listed in the technical description have to be followed.
  • For monitoring of water-polluting liquids and flammable liquids with a flash point < 55°C.

 

The leak detector must be mounted outside the hazardous area (ex-zone)!

IVF_1Operating Conditions

  • The media list in the technical description must be observed.
  • The leak protection lining in single-walled tanks must have a general building approval (certificate earlier).

 

Accessories

  • Installation of a potential free relay.
  • Installation in protective casing, with external heating and alarm.
  • Mounting Kits (MBS) for the corresponding container ports.

 

Function

  • Leak detector on the vacuum principle, with integrated pump.
  • The vacuum pump evacuates air from the interstitial space and blows it through the exhaust pipe to the exhaust valve of the container.
  • Based on the set switching values a trigger switch mounted on the measuring line controls: Pump ON / OFF, Alarm ON / OFF.

 

IIIF_3Operating vacuum:

in the interstitial space

max. -80 mbar +/- 5 mbar

Switching values: relative pressure

Alarm ON PAE = -34 mbar +0/-10 mbar

Pump OFF PPA = -80 mbar +/-5 mbar

For further data please see the Technical Description of the "VAKUMATIK IV F R34" leak detector.

 

Mounting Examples

Please click on the picture for a larger view!

IVF_bild_a

 

Documentation

ASF pdfTechnical Description IV F R34

ASF pdfData Sheet IV F R34

ASF pdfIV F R34 Accessories & Assembly Kits

Links

ASF linkAdvantages of the new design of the ASF leak detection systems